KEEP Instruction - Omron PLC Programming Tips
There is a better instruction available in CX-Programmer for such situation, CX- Programmer is the software used to program the Omron PLC, which can do your job easy. KEEP is the instruction name and in this instruction, we can define the SET and RESET conditions at same rung.
See the below picture.
Note:- Click on the picture for a clear view.
When W2.0 turns ON, the designated bit will go ON and stay ON until reset, regardless of whether W2.0 stays ON or goes OFF. When W3.0 turns ON, the designated bit will go OFF(w4.0).
Recommended Article: PLC Logic Auto-Filling Tank
How to Make Flip-Flop using KEEP Instruction in PLC
KEEP Instruction can be used to create flip-flops as shown below.
Note:- Click on the picture for a clear view.
If a holding bit is used for BIT to be SET, the bit status will be retained even during a power interruption. KEEP can thus be used to program bits that will maintain status after restarting the PLC following a power interruption. An example of this that can be used to produce a warning display following a system shutdown for an emergency situation is shown below.
Note:- Click on the Picture for a clear View.
Important Notes
i) If S and R are ON simultaneously, the reset input takes precedence.
ii) The set input (S) cannot be received while R is ON.